Robert J. Deissler1, Tanvir Baig1, Charles R. Poole1, David Doll2, Michael Tomsic2, and Michael A. Martens1
1Department of Physics, Case Western Reserve University, Cleveland, OH, United States, 2Hyper Tech Research Inc., Columbus, OH, United States
Synopsis
A numerical simulation of the heat equation was
performed for a 10 coil persistent mode 1.5 T MgB2 conduction-cooled
magnet. A hot spot was initialized by allowing a section of wire to become
resistive on one coil. An active
protection system consisting of surface heaters on all the coils was initiated
at 100 mV. Using a standard wire, the temperature was found to reach nearly 300
K, which may damage the coil. By increasing the amount of copper, using Glidcop
instead of Monel, or increasing the thermal conductivity of the insulation, the
temperature is kept within safe limits.Introduction
Conventional MRI machines use
superconducting magnets with niobium titanium (NbTi), requiring thousands of
liters of liquid helium to bathe the superconducting coils. Since helium is a costly
nonrenewable resource and in short supply, it would be desirable to have a conduction-cooled
superconducting magnet that avoids the use of a liquid helium bath. One such
candidate for a conduction-cooled magnet would use magnesium diboride (MgB
2)
superconducting wire. Compared to NbTi, which has a critical temperature of 10
K, MgB
2 has a critical temperature of 39 K. Although it is much more
difficult to initiate a quench in an MgB
2 magnet compared to an NbTi
magnet, it is also much more difficult to protect such a magnet if an
unintended quench does occur [1,2]. A passive quench protection system works
well for NbTi magnets whereas protection for an MgB
2 magnet would
require an active system. Here an active protection system is proposed for a
persistent mode 1.5 T MgB
2 magnet [2,3], and a numerical simulation
for the full 10 coil magnet is performed. If no protection system were present,
a localized hot spot would rapidly grow and damage the coil. By placing heaters
on the surfaces of all the coils, the heaters can be activated when a localized
hot spot is detected, thereby causing all the coils to rapidly quench. This
increases the resistance of the coils, thereby decreasing the current before
the hot spot causes damage. These same heaters can be activated in an emergency
to quickly bring the field to zero.
Methods
The heat equation is discretized in
space and then integrated in time using a 4th order Runge-Kutta
scheme (ODE45) in Matlab. Heaters are placed on the surfaces of all the coils.
A hot spot is initiated by letting a section of wire on the surface of coil 1
become resistive. When the voltage across coil 1 becomes greater than 100 mV
[4], the heaters are initiated. The total amount of energy input into the outer
layer of the coils is 34.4 kJ in 0.2 s, where the amount of energy input into
each coil is proportional to the outer surface area of that coil. The wire used
for the simulations is based on one from Hyper Tech Research, Inc [5]. In order
to bring down the maximum temperature so that the coil is not damaged,
variations of this wire are used in the simulations, which include adding more
copper, using Glidcop Al-60 [6] instead of Monel, and increasing the thermal
conductivity of the wire insulation.
Results
Figure 1a shows a plot of the maximum
temperature reached on each of the coils for the material percentages shown.
Since the hotspot was initiated on the surface of Coil 1, the maximum
temperature reached occurs on that coil. The vertical dotted line indicates the
time at which the detection voltage reaches 100 mV and the protection heaters
are initiated. The maximum temperature is seen to reach almost 300 K which may
damage the coil [1]. Increasing the amount of copper to 36% (Fig. 1b) is seen
to decrease T
max to about 180 K, which should be safe [1]. If
instead of increasing the amount of copper, the Monel sheath is replaced by
Glidcop (Fig. 1c), T
max reaches about 150 K, which is even better.
Another option is to increase the thermal conductivity of the insulation. By increasing
this quantity by a factor of 3 (Fig. 1d), T
max is decreased to about
180 K, which is again safe.
Conclusion
A numerical simulation of the heat equation was
performed for a persistent mode 1.5 T MgB
2 conduction-cooled magnet.
A hot spot was initialized by allowing a section of wire on the surface of Coil
1 to become resistive. An active protection system was employed using surface
heaters on all the coils, which were initiated when the voltage across Coil 1
became greater than 100 mV. Using the standard wire (15% Cu, 15% SC, 45%
Monel), the temperature was found to reach nearly 300 K, which may damage the
coil. By increasing the amount of copper, using Glidcop instead of Monel, or
increasing the thermal conductivity of the insulation by a factor of 3, the
temperature is kept within safe limits, the use of Glidcop giving the best performance.
Acknowledgements
The authors acknowledge the support of
the Ohio Third Frontier and NSF grant PFI:BIC 1318206.References
[1] Iwasa, Y. Case Studies in Superconducting Magnets
(Springer, New York, 2009).
[2] Poole, C. et al., Proc. Intl. Soc. Magn Reson. Med. 23, 1845 (2015).
[3] Baig, T. et al. Supercon. Sci. Tech. 27
125012 (2014).
[4] Huang, X. et al., IEEE Trans. Appl. Supercond. 20(3),
2091, (2010).
[5] http://www.hypertechresearch.com.
[6] Malagoli, A., et
al. IEEE Trans. Appl. Supercond. 19, 3670, (2009).