Yash-Veer Singh1, Juan A Sabate1, Ruxi Wang1, Viswanathan Kanakasabai2, Krishna Mainali1, and Huan Hu1
1GE Global Research, Niskayuna, NY, United States, 2GE GR JFW Technology Center, Bengaluru, India
Synopsis
The magnetic resonance imaging (MRI) gradient driver
is a high-performance inverter that provides large peak currents, >1000A,
for the gradient magnetic fields used for imaging. MR system has capacitors for
energy storage at the amplifier stage input voltages. Volume/weight reduction
in energy storage elements is one of the challenging issue in design of compact
and efficient MRI gradient system. It is possible to reduce capacitance value
in energy storage elements by synchronizing the control of the gradient driver different
subsystems. Control synchronization is achieved by providing reference value of
coil current simultaneously to the different controller of the MRI system.
Introduction
Gradient
amplifier (GA) to control magnetic field gradient in MRI scanners are switched
power amplifiers implemented with full bridge inverters connected in series
[1]-[2]. The amplifiers are fed from power supplies (PS) with multiple isolated
outputs. The pulsating power requirements for the gradient sequences make energy
storage a key component in the circuit structure of these gradient amplifiers
[3]-[4]. Volume/weight reduction in energy storage elements is one of the
challenging issue in design of compact and efficient MRI gradient system. The
energy storage elements between PS and GA act as a buffer during fast transients,
high di/dt. Energy storage at the input of the PS provides power support during
the imaging sequence. Power supply stage regulates the front-end
voltages of GA and delivers the power corresponding to the losses in the
gradient coil and the GA. Energy storage elements will supply peak power
demanded by the imaging sequence. It is possible to reduce capacitance value in
energy storage elements by synchronizing control different subsystems of MRI
scanner. Control synchronization is achieved by providing gradient coil current
refence to all the stages -GA, PS and PDU- controllers simultaneously to
calculate control response needed without waiting for the voltage dip
during normal operation. The synchronization helps to limit the peak power flow
from the utility with less capacitance.Method of Control Synchronization
Block
diagram of different subsystems in gradient chain of MRI system is shown in
Fig.1(a). Power distribution unit (PDU) is connected to the grid. This PDU can
be either low frequency transformer with taps on primary to serve different
input voltage conditions or it can be another power conversion stage (high
frequency). Each GA in Fig.1(a) has capacitive energy storage element, C1 for
GA-X. Conventionally independent controls are used in gradient chain of MRI
system as shown in Fig.1(a). These controllers utilize local reference value
and feedback signals to generate controller output. Synchronized control platform
as shown in Fig.1(b) enables faster calculation of required controller output
and reduces the energy storage need in gradient amplifier by supplying coil
current reference to all the different control blocks simultaneously. Schematic
of the synchronized control is shown in Fig.3. Common energy storage, either
capacitors or capacitor with electronic converter, is placed at the input of PS.
Mathematical model of loads in each of the power stages is included in the
control and reference value of coil current, Icoil_reference, is
used as common signal to all three controllers and processed with these
mathematical models to calculate feedforward control command for their
respective controller.Results and Discussion
Simulation of full gradient chain is designed in
PLECS (circuit simulator). Reference value of PS output voltage is 1250V dc. Output
voltage of PS drops by 75V on each dc port when coil current reference, 1300A
flat-top, is provided as shown in Fig.2(a). Using synchronized control, for the
same gradient coil current command, voltage dip in output voltage of PS is reduced
to 32V as shown in Fig.2(b). Because now voltage dip is reduced significantly
and therefore requirement of capacitance in dc link of amplifier also reduced.
For the same gradient coil current command and with 3 mF capacitance on each input
dc port of GA instead of 7mF, output voltage dip to 75V is shown in Fig.2(c). Synchronized
control enables reduction of capacitance in gradient amplifier.
A full-scale lab prototype has been tested. For
the same coil current reference (1300A flat-top), output voltage of PS falls to
192V in case of conventional controller and with passive energy storage of 54mF
in front of PS as shown in Fig.4(a). Voltage drop of 80V is noticed at the
output of HFPDU in the common ES stage. Simulation of the same test condition
is shown in Fig.4(b). Experimental results show good match with simulation
results.Acknowledgements
No acknowledgement found.References
[1] J.Sabate, et al., Proc. ISMRM. 2007. [2] R.Wang. et al., Proc. ISMRM 2018. [3] J.Sabate, et al., Proc. European
Power Electronics Conf. 2007. [4] Y.Singh,
et al., Proc. IEEE-Applied Power Electronics Conference 2013.